Commercial Property

FIRE SAFETY CHECKLIST FOR COMMERCIAL PROPERTIES

Amarillo FMO emblem

Mission Statement

Amarillo Fire Marshal’s Office strives to provide the citizens of Amarillo with a safe and secure environment while they are in any public buildings in the city limits of Amarillo. This checklist is intended to assist business owners and managers with the information to better protect their customers, property and emergency responders. The Fire Marshal’s Office encourages proactive inspections by the business owners and their management staff but this list does not take the place of annual inspections by Fire Marshal Staff nor does it take place of required inspections from licensed and certified inspectors. Amarillo Fire Marshal’s Office incurs no liability for providing the community with this checklist.  All items were taken from the International Fire Code 2012 ed. which was adopted by the City of Amarillo.  Any questions reference code can be directed to the Fire Marshal’s Office by email or contacted by phone at (806)378-4238.

Fire Protection Systems Inspection, Testing and Maintenance

  • Fire Alarm systems, sprinklers and fire pumps shall be inspected, test and serviced annually. (IFC901.6)
  • Records of all fire protection system inspections, tests and maintenance shall be kept on the premises for review by the Fire Official. (IFC 901.6.2)
  • Fire protection systems shall be maintained in an operative condition at all times. (IFC 901.6)
  • Emergency lighting and exit sign lighting shall be working properly at all times.(IFC 1006)
  • Emergency generator systems shall be routinely inspected, operated and serviced per NPFA 110 &111. All records shall be kept on the premises for review by the Fire Official. (IFC 604)
  • Commercial cooking fire protection systems shall be test at least every 6 months. (IFC 904.11.6.4)
  • Hoods, grease removal devices, fans ducts, etc. shall be cleaned to bare metal. Cleaning shall be recorded, and records shall state the extent, time and date of cleaning. Records shall be maintained on premises. (IFC 904.11.6.3)
  • Private hydrants shall be inspected, serviced and flow tested annually. (IFC 508.5.3)

Exits

  • Exit doors shall be unlocked when building is occupied. (IFC 1008.1.8)
  • Exit signs, doors, halls shall not be visually or physically obstructed by storage, decorations, furnishings, snow or ice. (IFC 1028.3&4)
  • Exit signs shall be illuminated. (IFC 1011.5.3, 1027.3)
  • Exit ways shall be illuminated at all times the building is occupied including during commercial power failures. (IFC 1006)
  • Fire doors, smoke dampers and other fire resistance barriers and assemblies shall not be modified or otherwise impaired from the proper operation at any time. (IFC 703)

 

Combustible and Flammable Material Storage

  • Combustible materials (cardboard, paper, plastics, kerosene, paint, etc.) shall not be stored in boiler rooms, mechanical rooms, or electrical equipment rooms. (IFC 315.2.3)
  • Combustible materials shall not be stored in exit ways, hallways, stairways or exit enclosures. (IFC 315.2.2)
  • Outside dumpsters shall be kept at least 5 feet away from combustible walls, windows, doors, overhangs and lid shall be closed. (IFC 304.3.3)
  • Combustible storage shall be at least 2 feet below the ceiling or 18 inches below sprinkler heads. (IFC 315.2.1)
  • Compressed gas containers, cylinders and tanks shall be secured to prevent falling. (IFC 3003.5.3)
  • Flammable materials (gasoline, propane, alcohol, etc.) shall not be stored indoors. Including fuel tanks of motorcycles, lawn-care equipment or cooking equipment, etc. (IFC313)

Building Maintenance

  • All private hydrants, fire lanes, fire department connections (FDC) and control valves shall be clear, labeled, visible and unobstructed, including snow and ice removal. (IFC 503, 508.5)
  • The building address shall be clearly visible from the street, minimum 4 inches in height with contrasting background. (IFC 505.1)
  • A knock box with all entrance and interior keys for emergency access is required for all structures that automatically dial 911. (IFC 506.1)
  • Fire-resistance-rated construction shall be maintained. (IFC 703.1)
  • Occupant load signs must be legible, permanent and posted in conspicuous location. (IFC 1004.3)
  • Door labels are required for accesses to electrical, furnace, sprinkler, mechanical, and generator rooms and to the roof. (IFC 510, 605.3.1)
  • Candles and other open flames are not permitted in commercial properties without special permission from the Fire Marshal. (IFC 308)

Electrical

  • A working space of not less than 30 inches wide (or width of equipment), 36 inches deep and 78 inches high shall be provided in front of electrical service equipment. No storage with this workspace. (IFC 605.3)
  • “Power strips or surge protectors” shall be UL listed, polarized, grounded and equipped with over current protection and shall be directly connected to a permanently installed receptacle. (IFC 605.4.1,.2)
  • “Power strips” cords shall not extent through walls, ceilings, floors, under doors, or floor coverings, nor be subject to environmental or physical damage. (IFC 605.4.3)
  • Extension cords, Multi-plug adapters and flexible cords shall not be a substitute for permanent wiring. (IFC 605.4,.5)
  • All electrical boxes shall be properly covered. (IFC 605.6)
  • Portable electric heaters shall be UL listed and plugged directly into a permanent wall receptacle, not into an extension cord, power strip or adapter. The must be positioned at least 3 feet away from combustibles. (IFC 605.10)

Portable Fire Extinguishers

  • A minimum of one 2A-10:BC portable fire extinguisher shall be provided within 75 feet of travel distance from anywhere in the business on each floor. (IFC 906.3)
  • A class K fire extinguisher shall be mounted within 30 feet of commercial food equipment using vegetable or animal oils. (IFC 904.11.5)
  • Fire extinguisher shall not be obstructed and all shall be in a conspicuous location. When visually obstructed, approved signs shall be provided to indication location and not obstructed. (IFC 906.5,.6)
  • Fire extinguishers shall be mounted on wall with hanger at least 4 inches above the floor and no more than 60 inches above the floor. (IFC 906.7)
  • Annual, certified inspections of all extinguishers are required. (IFC 906.2)